<i>ProReact</i> Digital Interface Units icon

ProReact Digital Interface Units

Providing additional functionality to digital linear heat detection
  • UL approved interface units
  • CE and UKCA certified for European markets
  • Can monitor up to two zones of digital linear heat detection cable
  • Contains alarm point distance location enabling users to quickly locate and respond to an incident
  • Optional interlock mode available

Frequently asked questions about ProReact Digital Interface Units

What are the power requirements of the ProReact Digital Interface Units?

Thermocable’s ProReact Digital Interface Monitor Module and the ProReact Digital Sensor Control Unit require a 24V power supply.

What is the ambient operating temperature range of the ProReact Digital Interface Units?

The recommended ambient operating temperature range is between -20°C and +50°C (-4°F – +122°F).

How do ProReact Digital Interface Units connect into an input/output module or fire alarm panel?

Please see below the information for the fire and fault outputs:
Fault condition
2x Form C volt-free relay contacts (resistive, common)
Max V – 30Vac or 42.4Vdc
Max Current – 2A
Max Switching Power – 60W, 62.5VA

Fire condition
2x Optoisolated phototransistor output (resistive, common)
Max V – 35Vdc
Max Current – 80mA
Max Power Dissipation – 150mW

What is the difference between the independent and interlock modes of operation?

Independent – This is when the interface unit is used as a two zone system. When a fault or overheat condition occurs on a Digital LHD zone, the corresponding fault or alarm output respectively is triggered. The two zones operate independently and both sets of outputs should be connected to a fire alarm control panel. If the zone is not required leave the 3.6kohm resistor in the zone input terminals as supplied. In this mode, the two zones can either contain identical rated temperature Digital LHD cables or two different rated temperature Digital LHD cables.

Interlock – this mode is for applications which require a fail-safe guarantee that an alarm is only triggered when an overheat condition has been detected. This mode may also be known as coincidence detection. In this case, the same rated temperature Digital LHD cable should be attached to both zones of the interface unit. The alarm output is only activated when both Digital LHD cables trigger an alarm due to an overheat condition. If one Digital LHD cable zone input registers an alarm but the second does not, the alarm output will not be activated. This is to prevent an alarm if a mechanical or other issue has triggered one Digital LHD cable and not an overheat condition.

Can I install non-sensing (or “leader”) cable between a ProReact Digital Interface Unit and the linear heat detection cable?

Yes. In certain applications it may be desirable or necessary to use non-sensing leader cable between a ProReact Digital interface unit and Digital LHD cable. For example, if the interface unit is located some distance away from the area protected by the Digital LHD cable. This may be required if the expected ambient temperature range, or other environmental conditions, where the Digital LHD cable is to be used is greater than the maximum ambient temperature range for the interface unit.

The maximum length of leader cable that can be used per zone is dependent upon the leader cable diameter. Please contact us if you require any further information.

What are the dimensions of the ProReact Digital Interface Units?

The ProReact Digital Interface Units are IP65 rated and measured as follows:
Height: 180mm x Width: 120mm x Depth: 60.5mm (H7.1in x W4.72in x D2.38in)

ProReact Digital Interface Units downloads

ProReact Digital Interface Units file

ProReact Digital Interface Monitor Module Installation Manual ProReact Digital Interface Units

Type : pdf Size : 2.09 MB Uploaded : Jun 30, 2022 Download now
ProReact Digital Interface Units file

ProReact Digital Sensor Control Unit Installation Manual ProReact Digital Interface Units

Type : pdf Size : 3.16 MB Uploaded : Jun 30, 2022 Download now
ProReact Digital Interface Units file

ProReact Digital Interface Monitor Module UL Certificate of Compliance ProReact Digital Interface Units

Type : pdf Size : 406.73 KB Uploaded : Jun 30, 2022 Download now
Sales Enquiry